|
All about fume hoods
Hoods used in conjunction with a heating or air conditioning
system as room exhaust, should generally be located on the opposite side of
the room from the inlet registers, discusses Salil Sansare, Head of Marketinng
Division, Labguard
What is a laboratory fume hood?
A laboratory fume hood is a ventilated enclosure where harmful
or toxic fumes of vapours can be handled safely. The purpose of the hood is
to capture, contain and remove contaminants, preventing their escape into the
laboratory. This is accomplished by drawing contaminants within the hoods
work area away from the operator, so that inhalation and contact are minimised.
Airflow into the hood is achieved by an exhaust blower which pulls
air from the laboratory room into and through the hood and exhaust system. This
pull at the opening of the hood is measured as face velocity. A
baffle, and other aerodynamically designed components control the pattern of
air moving into and through the hood. Contaminated air within the hood is then
diluted with room air and exhausted through the hoods duct system to the
outside where it can be adequately dispersed at an acceptably low concentration.
Laboratory exhaust systems and types of laboratory hoods
All laboratory fume hoods operational airflow can be
described as one of two types: conventional and by-pass. Auxiliary-air and variable
air volume (VAV) hoods are variations of the by-pass hood. All the types of
hoods are described below:
Conventional
The conventional hood is a basic enclosure with an interior baffle and movable
front sash. The conventional hood generally operates at a constant exhaust volume
with the majority of exhaust air entering the hood through the sash opening.
Closing the sash increases the speed of the air through velocities are to be
expected with the sash in the near closed position (figure 1).
The conventional hood is generally the least expensive, but its performance
depends largely on sash position.
With the sash in the near closed position, high velocity air passing position,
high velocity air passing through the sash opening can damage fragile apparatus,
disturb instrumentation, slow distillation rates, cool hot plates, disperse
valuable sample materials or result in turbulence inside the hood. Conventional-type
hoods comprise the majority of hoods in the market.
By-pass
The by-pass hood generally operates at a constant volume and is designed so
that as the sash is closed, the air entering the hood is redistributed, thereby
minimising the high velocity air streams encountered in conventional hoods.
The by-pass openings above and below the sash is raised or lowered (figure 2).
Therefore, the face velocity in by-pass hoods does not generally reach levels
which might be detrimental to lab fume hood procedures.
Auxiliary-Air
A variation of the by-pass hood, the auxiliary-air hood offers a means of providing
up to 50 per cent of the air for the hood exhaust from outside the laboratory,
and limits the volume of tempered air removal from the laboratory (figure 3).
This hood type has many names including induced air, add-air, balanced air and
make-up air.
One advantage to auxiliary air hoods is that they feed air-starved
laboratories, where room supply air volume is not adequate to support a laboratory
hood. Another advantage to auxiliary-air is that, when properly applied, it
can provide energy saving by limiting the volume of cooled room air exhausted
by the hood. The level of savings depends on the degree to which the auxiliary
air must be tempered.
| |
Stain Resistance
|
Moisture Resistance
|
Chemical Resistance
|
Heat Resistance
|
Flame Resistance
|
Other Comments
|
| Poly-Propylene (PP+FRP) |
Very Good |
Excellent |
Excellent |
Average |
Fire-retardant |
Most preferred linear |
| PolyvinylChloride (PVC) |
Very Good |
Excellent |
Excellent except for some
solvents |
Average |
Fire-retardant |
Wellsuited forsulfuric and
hydrofluoricacid digestion |
| Stainless steel (Type 316)
|
Good |
Excellent |
Good resistance to a wide
range. Subject to attackby some acids |
Excellent |
Excellent |
Primarily used for special
applications involving perchloric acid or radioisotope |
|
Task to be performed
|
Recommended liner
|
| Biological work-Chemicals only |
PP + FRP |
| Radiological Work |
SS 316 |
| Digestion-HF |
PVC |
| Drug Synthesis |
PP + FRP |
| Biological Work- Virulent or Toxic Materials |
SS 316 |
| Chemical Research |
PP + FRP |
| Chromatography |
PP + FRP |
| Classroom Use-General Chemical |
PP + FRP |
| Cosmetic Research-General |
PP + FRP |
| Digestion- Acids (except HF and Perchloric) |
PP + FRP |
| Fine Powders-General Chemistry |
PP + FRP |
| Fine Powders-Toxic or radioactive materials |
SS 316 |
| Food and Beverage-R&D or Quality Control |
PP + FRP |
| Hospital-Virulent or Radioactive Material |
SS 316 |
| Instruction/Demonstration- General Chemistry |
PP + FRP |
| Perchloric Acid |
SS 316 |
| Petrochemical-Flammable |
SS 316 |
| Petrochemical-Non Flammable |
PP + FRP |
| Pharmaceutical-Production Run |
PP + FRP |
| Pharmaceutical-Research |
PP + FRP |
| Pilot Plant Synthesis Simulations |
PP + FRP |
| QC Industrial |
PP + FRP |
| QC Industrial-Flammable |
SS 316 |
VAV Fume Hoods
VAV
Fume hood represents higher level of fume hood safety and energy efficiency
over other type of fume hoods. It can dramatically reduce the volume of air
being extracted from the laboratory while still retaining the required airflow,
through the open sash. Salil Enterprises VAV system alters the exhaust
volume using a damper that opens and closes based on airflow and sash position
By reducing the air volume exhausted when the sash in lowered, VAV control offers
significant energy saving opportunities.
Walk-in Fume Hoods
This hood accommodates laboratory procedures that require
cumbersome equipment or maximum work area. It directly mounts on floor and uses
the laboratory floor as the bottom work surface. Each hood is provided with
water tap and gas service fixtures, easy moving sash and appropriate illumination
arrangement.

Special Application Laboratory Fume Hoods
Unique features may be added to the hood and exhaust system to accommodate special
procedures in the hoods. Below are description of a few of the special purpose
hoods offered:
Perchloric-Acid Hoods: Perchloric acid hoods are dedicated
for use with perchloric acid only. Organic materials should not be used in a
perchloric acid hood because an explosion may occur when perchloric acid reacts
with organic materials. It must be constructed of relatively inert impervious
materials such as type 316 stainless steel or polyvinly chloride (PVC) or ceramic-coated
materials. Hoods used for these application have integral work surfaces, covered
interiors and a drain for easy and through cleaning. Washdown features are required
since the hood and duct system must be thoroughly rinsed after each use to prevent
the accumulation of potentially reactive perchloric salts. Horizontal ducts
runs and sharp turns are avoided so that washdown residue drains thoroughly.
Each perchloric acid hood requires its own dedicated exhaust system with washdown
capability.
Radioisotope Hoods: Hoods used for radioactive applications
have integral work surfaces and covered interiors to facilitate decontamination.
Liner materials such type 316 stainless steel, are impermeable to radioactive
materials. Cupsinks are provided in the integral work surface. The safe disposal
of radioactive effluents should be observed. These hoods are sturdy enough to
support lead shielding bricks in instances where they are required. They can
also be installed to facilitate the use of High Efficiency Particulate Arrester
(HEPA) filter in the ductwork. The laboratorys competent authority should
determine which (if any) filters are required to trap the radioactive materials
emitted during a particular applications.
Laboratory Hood Specification
Hood
Size: The working space inside a laboratory hood is defined as that part
of the hood interior where apparatus is set up and vapours ar generated. The
working space required deter-mins the width of the hood needed. One sources
recommends that 5 linear feet of hood space be provided for every two workes
if they spend most of their time working with chemicals.
Laboratory hood sizes are commonly expressed by the outside width and not by
working space. The most common hood widths are 4,5 and 6 feet. 4 feet models
are ideal as individual work stations whereas 5 feet models are spacious enough
to handle huge apparatus. 6 feet models prove to be excellent choice when greater
ventilated workspace is required. Dept of all models remain constant. Custom
designed fume hood may have large widths. The actual working space is approximately
3 to 10 less than the expressed width of the hood, depending upon
the size.
Hood Linear Materials
The liner materials selected should be durable and resist chemicals, heat and
open flame. A description of common liner materials and their characteristics
follows (table 1).
The best liner materials for a hood should be determined by the applications,
types and concentration of chemicals, gases, vapours, fumes or smokes and qualitatively
as fume acids, alkalis, solvents or oils. Hood liners are subjected to attack
from such effluents by corrosion, dissolution and melting.
Compatibility chart (table 2) is intended as a guide for selection of right
liner material. Please select the liner suitable to your tasks.
Work Tops
It is the actual surface on which the reactions are carried
out. It is fabricated to contained spillage and splashes. Apart from regular
PP, PVC, SS 316 work surfaces; following options are also available:
Ceramic Tiles
- Most preferred option
- Highly resistant to aggressive chemicals
- Excellent stain and heat resistance
Granite
- Hard and uniform surface
- Moderately resistant to aggressive chemicals
- Excellent stain and heat resistance.
Sashes
Sashes provide physical protection from splashes and reactions
and are transparent to allow viewing. Sashes rise vertically, slide horizontally
or combine both: horizontal and vertical characteristics. (figure 7,8 and 9)
Sash configuration selection is a matter of preference. Vertical rising sashes
are the most popular and allow large apparatus to be loaded in the hood. Horizontal
sliding sashes allow the operator to reach around both sides of the sash while
using the sash as shield. Because the sash opening is smaller, they conserve
energy by limiting the volume of air exhausted.
Service Fixtures
Utility services include connections to gases, air, water and vacuum. If service
fixtures are required, they are installed to allow the connection of service
supply lines on the hood itself. All service valves are accessible for maintenance.
Inner those connectors are corrosion resistant. For safety and convenience,
all service fixtures and remotely controlled from outside the hood and clearly
identified with different colours.
Electrical Receptacles
Electrical receptacles are located on the hood exterior, away from the corrosive
effects of the fumes inside the hood structure. Provisions are made so that
all electrical wiring is isolated and physically separated from vapours handled
within the hood.
Lighting
Light fixtures are Vapour-proof. These light fixtures are fluorescent, installed
outside the hood liner and protected from the hood interior by a transparent,
impact - resistant shield. Access for replacing or cleaning is from the exterior
whenever required.
Centrifugal Blowers
Of
all the additional components needed, the blower is the most crucial to the
performance of the hoods. Fume hood installations utilizing remote blowers are
the most common type. Since the entire duct length is under negative air pressure,
any leakage in the duct is drawn in and contained rather than pushed out into
the building environment. The exhaust blower is positioned on the buildings
exterior, usually on the roof, where noise is less noticeable. By creating suction
within the ductwork, blowers draw air from the laboratory room, through the
hood and out the duct system. Blowers components are constructed from a variety
of materials to resist corrosion from chemical fumes. Impellers are made of
stainless steel or PVC or PP as per model specifications. For weather proofing,
roof-mounted blowers have protective housings.
Fire Extinguishers
Hoods can be scenes of fires due to the nature of some applications. We offer
fire extinguishers that mount adjacent to the hood and can be used at the emergency
providing round the clock protection. ABC Dry powder extinguishers are most
preferred.
Ductwork
Ductwork includes rigid and flexible pipes, couplings, elbows, reducers and
weather cap. Round diameter duct offers the least static resistance. Like the
liner materials of a laboratory hood, duct materials must be resistant to the
fumes exhausted through it. Hence usually ductwork of similar liner material
is used.
Optional Accessories
Base Cabinets
Fume
hoods are designed to rest on a bench-high base stand or cabinet. Existing platform
may be used as long as it provides adequate depth and height for the structural
support of the hood. Special base cabinets of powder coated steel are available
to store chemicals.
Base Stand
The base stand supports fume hoods. It is constructed out of corrosion resistant
epoxy polyester coated steel and equipped with adjustable foot rests. Available
in various sizes.
Airflow Monitor
Face
velocity measurements are often used to gauge the fume hoods ability to
contain and exhaust harmful vapours. Standards written by NFPA, ANSI and eve.
U.S. OSHA require specific acceptable fume hood face velocities, with local
alarms to warn if face velocities drop to an unsafe level.
To ensure the safety of fume hoods, Salil Enterprises
airflow monitors directly measure the average face velocity. Its sensor, mounted
on the fume hood, detects face velocity disturbances caused by moving sash,
splash shield use, or even user standing in front of the hood. If the face velocity
falls outside the acceptable range, audible and visual alarms warm users of
unsafe condition.
Fume scrubber
Fumes exhausted from fume hoods are usually disposed of by dilution into the
atmosphere. Scrubber uses water as the scrubbing liquid and incorporates a water
purification procedure. The chamber contains one or more spray nozzles. It produces
water jets across the chamber, providing liquid screen and causes impact with
dispersoids dropping them from the gaseous waste. The scrubber removes particles,
aerosols and gases, performing most effectively with latter if they have a high
solubility in water.
Planning Lab Space
The planned location of the fume food within the laboratory
affects both the safety and convenience of the user and the airflow patterns
of the room.


Keep these basics in mind when planning your space:
- Hoods should not be located near windows, doors
or air conditioning registers because potential cross drafts will interfere
with the airflow in to the hood.
- Never locate the hood adjacent to an exit or where
the user would forced to work in a high traffic area.
- If a common exhaust or supply system is used for
several hoods, the fume hoods should be arranged to require a minimum amount
of ductwork.
- Hoods used in conjunction with a heating or air
conditioning system as room exhaust, should generally be located on the opposite
side of the room from the inlet registers. The air from the registers should
sweep through the laboratory first, then be exhausted through the hood for
both safety and HVAC efficiency. (see diagram for an example).
 |
Basic Features |
- Aerodynamic design
- Automatic by-pass type air flow
- Interior of selected liner with preset
baffle
- Exterior of powder coated steel with S.
S corner covers
- Sink and drain arrangement with a tap
- Two remotely operated service fixtures
for gasses
- Flourescent lights with vapour proof fitting
- Counter-balanced easy moving sash
- Two electrical points with blower switch
and light switch on front fascia
- Silent blower of suitable capacity*
- Flow control valve to regulate airflow
- Fire extinguisher
|
|
|
- Aerodynamic design
- Aerodynamic Design
- Auxillary type air flow
- Interior of selected liner with preset
baffle
- Exterior of powder coated steel with S.
S corner covers
- Sink and drain arrangement with a tap
- Two remotely operated service fixtures
for gasses
- Flourescent lights with vapour proof fitting
- Counter-balance easy moving sash
- Two electrical points with blower switch
and light switch on front fascia
- Silent blowers (2 Nos.) of suitable capacity*
- Flow control valve to regulate airflow
- Fire-extinguisher
|
| * Blower suction capacity (CFM) and
motor power (HP) vary with hood width. Our blowers are designed for maximum
efficiency at minimal power consumption |
E-mail:labguard@vsnl.net
|